INC
TECHNOLOGY CO.,LTD.
Products page
ABB

specification
| ACS550 - 01 - 03A3 - 4 + B055 | |
| Mains connection | |
| Voltage and | 3-phase, 380 to 480 V, +10/-15%, 0.75 - 355 kW |
| power range | 3-phase, 200 to 240 V, +10/-15%, 0.75 - 75 kW |
| Auto-identification of input line | |
| Frequency | 48 to 63 Hz |
| Power factor | 0.98 |
| Motor connection | |
| Voltage | 3-phase, from 0 to USUPPLY |
| Frequency | 0 to 500 Hz |
| capability | |
| (constant torque at a max | |
| ambient temperature of 400c) | |
| Overload capacity | At normal use 1.1 x I2N for 1 minute |
| (at a max. ambient | every 10 minutes |
| temperature of 400c) | At heavy-duty use 1.5 x I2hd for 1 minute |
| every 10 minutes | |
| Always 1.8 x I2hd for 2 seconds every | |
| 60 seconds | |
| Switching frequency | |
| Standard | Default 4 kHz |
| Selectable | 0.75 - 90 kW 1 kHz, 4 kHz, 8 kHz |
| up to 355 kW 1 kHz, 4 kHz | |
| Acceleration time | 0.1 to 1800 s |
| Deceleration time | 0.1 to 1800 s |
| Environmental limits | |
| Ambient temperature | |
| -15 to 40oC | No frost allowed |
| 40 to 50oC | fswitch 4 kHz, derating please contact supp |
| Altitude | |
| Output current | Rated current available at 0 to 1000 m |
| reduced by 1% per 100 m over 1000 m to 2000 m | |
| Relative humidity | lower than 95% (without condensation) |
| Protection class | IP 21 or IP 54 |
| Enclosure colour | NCS 1502-Y, RAL 9002, PMS 420 C |
| Contamination levels | No conductive dust allowed |
| Transportation | IEC60721-3-1, class 1C3 (chemical gases), |
| Class 1S3 (solid particles) | |
| Storage | IEC60721-3-2, Class 2C3 (chemical gases), |
| Class 2S3 (solid particles) | |
| Operation | IEC60721-3-3, Class 3C3 (chemical gases), |
| Class 3S3 (solid particles) | |
| Programmable control connections | |
| Two analog inputs | |
| Voltage signal | 0 (2) to 10 V, Rin > 312 kΩ single-ended |
| Current signal | 0 (4) to 20 mA, Rin = 100 Ω single-ended |
| Potentiometer reference value | 10 V ±2% max. 10 mA, R < 10 kΩ |
| Maximum delay | 12...32 ms |
| Resolution | 0.10% |
| Accuracy | ±1% |
| Two analog outputs | 0 (4) to 20 mA, load < 500 Ω |
| Auxiliary voltage | 24 V DC ±10%, max. 250 mA |
| Six digital inputs | 12 V... 24 V DC with internal or external |
| supply, PNP and NPN | |
| Input impedance | 2.4 kΩ |
| Maximum delay | 5 ms ± 1ms |
| Three relay outputs | |
| Maximum switching voltage | 250 V AC/30 V DC |
| Maximum switching current | 6 A/30 V DC; 1500 V A/230 V AC |
| Maximum continuous current | 2 A rms |
| Serial communication | |
| RS 485 | Modbus protocol |
| Protection limits | |
| Overvoltage trip limits | |
| Running V DC | 842 (corr. to 595 V input) |
| Start inhibit V DC | 661 (corr. to 380 - 415 V input), |
| 765 (corr. to 440 to 480 V input) | |
| Undervoltage trip limits | |
| Running V DC | 333 (corr. to 247 V input) |
| Start inhibit V DC | 436 (corr.to 380 - 415 V input), |
| 505 (corr. to 440 - 480 V input) | |
| Product compliance | |
| Low Voltage Directive 73/23/EEC with supplements | |
| Machinery Directive 98/37/EC | |
| EMC Directive 89/336/EEC with supplements | |
| Quality assurance system ISO 9001 and Environmental system ISO 14001 | |
| CE, UL and cUL approvals | |
| EMC (according to EN61800-3) | |
| 1st environment restricted distribution with 30 m cable as standard | |
| 2nd environment unrestricted distribution with 100 m cable as standard | |
| For longer motor cable lengths, external EMC filters are available on request | |